Suite 2.01, 2nd Floor,
Kompleks Hamodal 1,
Persiaran Lagun Selatan,
Off Jalan Kewajipan,
SS 13/1K, 47500 Subang Jaya,
Selangor, Malaysia.
+603 5613 1850
+603 5613 1849
Previous | 2 / 9 | Next |
Conductor |
(Cu) Plain annealed stranded copper conductor Class 2, IEC 60228, BS6360 |
Fire proof layer |
(MGT) Mica glass tape |
Insulation |
(XLPE) Cross-linked Polyethylene |
Pairing / Twining |
Two/Three/Four insulated cores are cabled together and covered with a polyester tape wrapping |
Assembly |
Multiple pairs/triads/quads are cabled together, supplied with non-hygroscopic filler (optional) to obtain a circular construction and covered with a polyester tape wrapping |
Overall Screen |
(OS), Min. 20% overlap of aluminium backed polyester tape in contact with 0.5mm² (16/0.20mm) tinned annealed drain wire followed by a polyester tape wrapped over the screening tape |
Bedding |
(LSHF) Low Smoke Halogen Free -Black |
Armouring |
(SWA) Galvanized Steel Wire Armour |
Outer Sheath |
(LSHF-AT-AR) Low smoke zero halogen compound with anti-termite and anti-rodent additives. Black (Optional: Blue colour for Intrinsically Safe) |
Insulation color |
1 pair in Black & White
|
Reference Standard |
BS EN 50288-7 |
Voltage |
500V |
Max Operating Temperature |
+90ºC |
Halogen Free |
IEC 60754 |
Low Smoke Emission |
IEC 61034 |
Fire Integrity |
IEC 60331-21 |
Flame Retardant |
IEC 60332-3-22 |
Max. Conductor Resistance |
≤7.6Ω/km at 20°C(2.5mm²)
|
Max. Mutual Capacitance(at 1 KHz) |
≤ 85pF/min (1.5-2.5 mm²)
|
Max. L /R Ratio |
≤ 40pF/min (1.5-2.5 mm²)
|
Test Voltag |
2000Vac for 1 minute |
Bending Radius |
10 x overall diameter |