Conductor material | (CU) Plain annealed stranded circular copper conductor, Class 2 |
Fire proof layer | (MGT) Mica tape to IEC60331-21/SS229-1/BS6387 |
Insulation | (XLPE) Cross-linked polyethylene, XLPE |
Pairing / Twining | Two/Three/Four insulated cores are cabled together and covered with a polyester tape wrapping |
Overall Screen | (OSCR), Min. 20% overlap of aluminium backed polyester tape in contact with 0.5mm² (16/0.20mm) tinned annealed drain wire followed by a polyester tape wrapped over the screening tape |
Outer sheath | (LSHF-AT-AR) Low smoke zero halogen compound with anti-termite and anti-rodent additives and UV stabilizer. |
Applicable standards | |
Design standard: Conductor standarf: Flame propagation: Fire integrity: Acid gas emission: Smoke emission: |
IEC 60502-1 IEC 60228, BS 6360 IEC 60332-3-22 IEC 60331-21, SS299-1/BS6387 Cat. CWZ IEC 60754-2 IEC 61034 |
Sheath colour | Orange or Red |
Core identification |
1-pair : Black, White Multipair : Black, white with pair numbering (on each core) 1-trial : Black, White, Red Multi-trial : Black, White, Red with trial numbering (on each core) |
Printing | Yes |
Rated voltage | 500V |
Min. insulation Resistance @ 20ºC | 1000MΩ.km |
Test voltage | 2KV/1 min |
Max. conductor temperature | 90°C |