Suite 2.01, 2nd Floor,
Kompleks Hamodal 1,
Persiaran Lagun Selatan,
Off Jalan Kewajipan,
SS 13/1K, 47500 Subang Jaya,
Selangor, Malaysia.
+603 5613 1850
+603 5613 1849

| Previous | 4 / 4 | Next |
| Conductor material | (CU) Plain annealed stranded circular copper conductor, Class 2 |
| Fire proof layer | (MGT) Mica tape to IEC60331-21/SS229-1/BS6387 |
| Insulation | (XLPE) Cross-linked polyethylene, XLPE |
| Pairing / Twining | Two/Three/Four insulated cores are cabled together and covered with a polyester tape wrapping |
| Overall Screen | (OSCR), Min. 20% overlap of aluminium backed polyester tape in contact with 0.5mm² (16/0.20mm) tinned annealed drain wire followed by a polyester tape wrapped over the screening tape |
| Outer sheath | (LSHF-AT-AR) Low smoke zero halogen compound with anti-termite and anti-rodent additives and UV stabilizer. |
| Applicable standards | |
|
Design standard: Conductor standarf: Flame propagation: Fire integrity: Acid gas emission: Smoke emission: |
IEC 60502-1 IEC 60228, BS 6360 IEC 60332-3-22 IEC 60331-21, SS299-1/BS6387 Cat. CWZ IEC 60754-2 IEC 61034 |
| Sheath colour | Orange or Red |
| Core identification |
1-pair : Black, White Multipair : Black, white with pair numbering (on each core) 1-trial : Black, White, Red Multi-trial : Black, White, Red with trial numbering (on each core) |
| Printing | Yes |
| Rated voltage | 500V |
| Min. insulation Resistance @ 20ºC | 1000MΩ.km |
| Test voltage | 2KV/1 min |
| Max. conductor temperature | 90°C |